| Fig-Split Type AC Wiring Diagram |
What is the Split Type AC (Air Conditioner) Wiring Diagram?
A split AC or air conditioner has two main assemblies: the indoor unit (evaporator, blower, PCB) and the outdoor unit (compressor, condenser fan, contactor/capacitor). They are connected by a power supply and a multi‑core interconnecting cable that carries power, earth, and control/communication signals between the two units.
Key components and their electrical connections for Split Type AC (Air Conditioner)
- Main power supply
- Single‑phase 220–240 V (or 110–120 V in some markets) feeds the outdoor unit or a dedicated breaker/isolator; some systems feed the indoor unit instead—follow the manufacturer's diagram.
- Interconnecting cable (indoor ↔ outdoor)
- Typical cores: Live (L); Neutral (N); Earth (E); Signal/communication (S) or control. Some mini‑splits use 3‑core (L, N, E) plus a separate low‑voltage control pair; others use 4–5 cores for power + communication.
- Protection devices
- MCB / fuse on the supply; isolator/disconnector near the outdoor unit; surge protection recommended for outdoor compressor.
- Outdoor unit internals
- Compressor motor (to contactor/relay), run capacitor, overload protector, condenser fan motor, and the outdoor PCB that interfaces to the indoor PCB via the signal wires.
- Indoor unit internals
- Fan motor, evaporator thermistor(s), PCB (control board), display/remote receiver; the indoor PCB sends/receives commands and status over the communication pair.
Typical wire color/function table for Split Type AC Wiring
|
Wire |
Typical color |
Function |
|
L (Live) |
Brown; Red |
Main phase to the motors/contactor |
|
N (Neutral) |
Blue; Black |
Return conductor for the AC supply |
|
E (Earth) |
Green/Yellow |
Protective earth |
|
S (Signal/Comm) |
White; Yellow; Grey |
Control/communication between PCBs |
Typical wiring layout (step‑by‑step) for a split-type AC wiring diagram
- Isolate power at the distribution board.
- Run supply cable from a dedicated breaker/MCB to the outdoor unit isolator (or indoor unit if specified). Size cable per rated current.
- Run an interconnecting multi‑core cable between the indoor and outdoor units through the refrigerant pipe chase. Include an earth conductor.
- Connect supply to outdoor unit: L → outdoor supply terminal; N → neutral terminal; E → earth terminal. Fit MCB/fuse as required.
- Connect the interconnect to the indoor unit: match L, N, E, and signal wires to the indoor PCB terminals (labelled L, N, E, CN/COM/Signal). Ensure polarity and terminal labels match the manufacturer's diagram.
- Verify control wiring: the communication pair must be connected to the correct indoor/outdoor PCB terminals (often labelled TX/RX, CN, or COMM).
- Earthing: bond both units to the same protective earth. Test continuity.
- Power up and test: check MCB, measure supply voltage, run the unit through modes, and verify compressor start, fan operation, and remote/thermostat control.
Cable sizing and protection (practical guidance)
- Cable size depends on unit rated current and run length. As a rule of thumb, small split units (<2.5 kW) often use 2.5 mm² for power; larger units require 4 mm² or 6 mm². Always calculate using the unit’s nameplate current and local wiring regulations.
- MCB rating should match the unit’s full‑load and starting current per the manufacturer. Use a time‑delay fuse or appropriately rated MCB for compressor inrush.
Safety, common mistakes, and troubleshooting tips for split-type AC wiring
- Always follow the manufacturer’s wiring diagram — terminal labels vary by brand and model.
- Do not omit earth; lack of proper earthing is a major safety hazard.
- Wrong signal wiring (swapped comm pair) causes communication faults; check LED fault codes on PCBs.
- Voltage checks: measure the supply at the unit before connecting; low voltage can prevent the compressor from starting.
- If the unit trips the breaker on start, check capacitor health, contactor wiring, and correct MCB sizing.
Quick reference checklist before powering up the air conditioner
- Dedicated breaker/MCB installed and labelled.
- Interconnecting cable cores are correctly matched and secured.
- Earth continuity verified between indoor and outdoor units.
- Manufacturer terminal labels confirmed and followed.
- Surge protection and isolator fitted if required.
No comments:
Post a Comment
WAZIPOINT:
Thank you very much to visit and valuable comments on this blog post. Keep in touch for next and new article. Share your friends and well-wisher, share your idea to worldwide.