Showing posts with label Electrical network. Show all posts
Showing posts with label Electrical network. Show all posts
Wednesday, January 1, 2025
What Happen If Cables Placed In Magnetic Metal Conduit
Labels:
Cable-Engineering,
Electric power,
Electric power distribution,
Electric power transmission,
Electrical network,
High voltage,
Power cable
Location:
Dhaka, Bangladesh
Tuesday, October 15, 2024
ARMOUR EARTHING ASSEMBLING FOR SINGLE CORE CABLE
Armour Earthing Assembly for Wire Armour Single Core Cable
33kV Cable Earthing System |
Cable armour earthing is important for medium voltage (MV), high voltage (HV) and extra high voltage (EHV) system.
Our discussion on this article is limited only single core plastic or paper cable wired armour earthing procedure for medium voltage (MV) system or 7.2 kV to 36 kV ranges.
The crystal clear step-by-step assembly figure shown the complete procedure of earthing system for wired armour cable.
If you follow the shown 9 step carefully, we hope you will be able to assemble the cable armour earthing successfully.
9 Step to Earth Cable Armour
Sponsored:
- First of all remove the over-sheath according to the dimension given the appropriate manufacturer Installation Instruction, Remove the armour according to dimension as per shown in the drawing. Clean the end of the over-sheath for a length of 250 mm.
- Then slide the outer sleeve over the cable, and disassemble the clamping rings. Slide one clamping ring lug-downwards over the cable as shown in the figure 2.
- Following the figure no-3 spread the armour wires as shown in the drawing and screw the other clamping ring loosely to the lugged clamping ring.
- Install the termination in accordance with the Installation Instruction of termination manufacturer. Pass the end of the earth lead down through the clamping rings and connect it to one lug of the clamping ring. Tighten the clamping rings, refer to figure no-4.
- With a small overlap and slight tension wrap two layers of sealant tape round the overs-heath for a length of 50 mm, just below the armour wire ends. Wrap two layers of sealant tape round the earth conductor so that it will be just below the armour wire ends. Attach the earth conductor to the other lug of the clamping ring as figure-5.
- As shown in figure-6, bend the armour wires back and bind the ends to the over-sheath with a wire binder or plastic tape. noted that all sharp wire ends must be covered with plastic tape.
- With a slight tension and small overlap wrap two layers of sealant tape over the lower end of the termination for a length of 50 mm.
- Position the top end of the outer sleeve level with the top of the sealant tape. Shrink it into place starting at the center. Shrink the lower end first and work towards the upper end.
- Yes, you have done; installation of earthing assembly for armour is completed.
This is the basic instruction for cable armour earthing, to do it physically you must follow the manufacturer installation instruction and necessary safety code. If it is helpful, then share with others to help them.
Labels:
Cable,
Cable-Engineering,
Electric power transmission,
Electrical network,
High voltage,
Power cable,
UG Cable Project
Location:
Dhaka, Bangladesh
Wednesday, January 17, 2024
What Is the Voltage Classification?
Nominal Voltage Classification in Transmission and Distribution System
To identify the voltage level effortlessly in a transmission and distribution system a significant voltage classification is essential. The voltage class is used not only to identify the level of system voltage, but the main importance is to classify the Apparatus voltage ranges for the operation and maintenance of an electrical energy transmission and distribution system.
Labels:
Electric,
Electric power,
Electric power distribution,
Electric power transmission,
Electrical network,
Electrical-Engineering,
Electricity
Location:
Dhaka 1216, Bangladesh
Thursday, December 14, 2023
Why Does Single-Phase Require a Neutral Conductor but not in Three-Phase?
Do you think about why single-phase electricity requires a neutral conductor while three-phase electricity does not?
In a single-phase electrical system, power is transmitted using two conductors: the live conductor (carrying current) and the neutral conductor (completing the circuit). The neutral conductor is necessary to complete the circuit and provide a return path for the current back to the source.
Labels:
Earthing or Grounding,
Electrical network
Sunday, April 16, 2023
ALARM EQUIPMENT DETAILS FOR HV & EHV POWER TRANSMISSION SYSTEM
Fig: Fire drill in an airport |
Alarm Equipment Associate with Power Control Panel in Transmission Grid Station
Where an alarm system is specified in this article, especially for High Voltage transmission grid and normal Voltage Distribution substation, it should consist of an initiating device, a display unit, and push buttons mounted on the front of the appropriate control panel, together with a continuously rated audible warning device flasher unit and relays. The relays should wherever possible, be mounted inside the same panel; where the number of alarms to be displayed makes this impracticable, a separate alarm relay cubicle or cubicles will be considered as an alternative.
Multiple Alarm Tone
Where it is necessary to differentiate between the urgency of alarms then various approved alarm tone devices should be provided in this Contract. In addition and where specified an alarm beacon to the approval of the Engineer should be provided.
Location:
Mirpur, Bangladesh
Thursday, February 16, 2023
MCB: MINIATURE CIRCUIT BREAKER OPERATION BASIC
What is MCB?
MCB is a device designed to protect an electrical circuit's wiring from the serious damage which would be caused if it has to carry a current that is too high for the diameter of its wires.
The MCB or Miniature Circuit Breaker is actually working for both electrical circuits' make or break switch and protection device fuse.
Likely normal fan/light switches, MCB also can operate manually as circuit ON or OFF; its specialty is, it can break the circuit automatically to protect from overcurrent.
Fuse is the very first protection device for an electrical circuit. A fuse is actually nothing but a thin wire that is enclosed in a protective casing and plugged into the circuit.
Location:
Dhaka, Bangladesh
Sunday, January 15, 2023
SURGE ARRESTERS SPECIFICATION FOR 132 KV & 33 KV LINE
![]() |
Surge Arrester Specification |
Surge Arrester Requirements for 132kV and 33kV Underground Cable Line Projects
Surge arresters shall be of
the type employing non-linear metal oxide resistors without spark gaps. The
Contractor shall demonstrate by calculations that the surge arresters will
adequately protect the switchgear arrangement proposed.
Arresters shall be designed
and tested in accordance with the requirements of IEC 99 4. Any departure shall
be the subject of agreement between the Engineer and the Contractor. Routine
tests shall be carried out in accordance with the requirements of Section 15 of
this Specification.
Surge arresters shall be
housed in porcelain insulators designed to withstand extremes of the
environment described. The insulation shall have a minimum creepage distance of
25 mm/kV rated system phase-to-phase voltage. Porcelain shall comply with IEC
233. The method of sealing against the ingress of moisture shall be of a type
well proven in service and the manufacturing procedures shall include a practical leak test which can be demonstrated to the inspecting engineer if
required.
The internal components of
arresters shall be arranged to minimize radial voltage stresses, and internal
corona and to ensure minimal capacitive coupling with any conducting layer of
pollutant on the outside of the porcelain housing except where approved,
organic materials are not permitted.
Good electrical contact shall
be maintained between resistor blocks, considering any thermal expansion
and contraction of the block or mechanical shock during transport and erection,
by installing a well-proven clamping system.
Metal oxide arresters
installed outdoors shall be able to dissipate when new, twice the energy
generated in the resistor blocks when energized at their maximum continuous
operating voltage immediately having been subjected to the discharge duties
specified in IEC 99 4 and assuming that the porcelain housing and the
surrounding air is at least 5˚C higher than the maximum ambient air temperature
specified.
Good quality control of the
manufacturing process of the resistors shall be ensured by rigorous testing
procedures. The procedures shall ensure that the characteristics of the blocks
are, and will remain, within the specified limits when new and throughout the
anticipated life of the arresters. Samples may be selected at random by the
Engineer for special tests to be agreed upon with the manufacturer.
All surge arresters shall be
fitted with a pressure relief diaphragm which shall prevent explosive
shattering of the porcelain housing in the event of an arrester failure and the
arrester shall have been tested according to the high and low current tests
specified in IEC 99 1.
Arresters shall be supplied
completely for installation in an outdoor switchyard, including supporting
structures, insulating bases, and surge counters, one per phase, and, if
applicable, grading rings. The material used for terminals shall be compatible
with that of the conductors to which they are to be connected.
Each arrester shall be
identified by a rating plate in accordance with the requirements of IEC 99 4.
In addition, an identification mark shall be permanently inscribed on each
separately housed unit of a multi-unit arrester so that units can be replaced
in the correct position in the event of them being dismantled.
Surge counters shall have an
internal assembly that is matched to the line discharge capability of the
arrester and shall include a leakage current meter with a bilinear scale for
ease of reading. Auxiliary contacts are to be provided to signal remote
indications of the counter operation.
Sponsored:
Technical Data Schedule for 132 kV and 33 Surge Arrester
Sl. No.
|
Item no.
|
Unit
|
Nominal System Voltage
| |
132 kV
|
33 kV
| |||
1.
|
Manufacturer
| |||
2.
|
Model Number
| |||
3.
|
Type:
| |||
4.
|
Continuous operating voltage
|
kV RMS
| ||
5.
|
Rated voltage
|
kV RMS
| ||
6.
|
Standard nominal discharge current
|
kV
| ||
7.
|
Reference current at ambient temperature
|
mA
| ||
8.
|
Reference voltage for above
|
kV RMS
| ||
9.
|
Steep current impulse residual voltage
|
kV pk
| ||
10.
|
Lightning impulse residual voltage at
| |||
5 kA
|
kV pk
| |||
10 kA
|
kV pk
| |||
20 kA
|
kV pk
| |||
11.
|
Duty Class
| |||
12.
|
Discharge Class
| |||
13.
|
Pressure relief class
| |||
14.
|
Nominal Diameter of resistor blocks
|
mm
| ||
15.
|
Number of resistor blocks connected electrically in parallel
| |||
16.
|
Number of separately housed units pre-phase
| |||
17.
|
Overall height of arrester (without supporting structure)
|
m
| ||
18.
|
Overall height of arrester including grading ring if applicable
|
mm
| ||
19.
|
Clearances:
| |||
Phase to earth (from center line)
|
mm
| |||
Phase to phase (center line to center line)
|
mm
| |||
20.
|
Overall height of arrester (without supporting structure)
|
kg
| ||
21.
|
Maximum cantilever strength
|
Nm
| ||
22.
|
Maximum force due to the wind (at maximum specified gust speed)
|
Nm
| ||
23.
|
Minimum creepage distance over the insulator
|
mm
|
Labels:
Electric power distribution,
Electric power transmission,
Electrical network,
Electrical-Engineering
Location:
Dhaka, Bangladesh
Saturday, September 17, 2022
Emergency Restoration System for EHV & HV Power Transmission
ERS
is short for Emergency Restoration System, well known to the line crew of
national grid, and utility companies, and associated with other power transmission
and distribution companies. ERS structures are designed for quick bypassing and
restoring the transmission line in an emergency.
Why ERS Structure Is Required?
ERS Tower |
Damage
or breakdown is always unplanned. So, always a pre-planned is necessary to
overcome the breakdown within the shortest time. ERS structure is pre-fabricated for
quickly and safely bypassing damaged permanent structures; also ERS structures
allow us to rebuild or replace the permanent structures with minimum time
constraints.
What Is Terrain ERS Tower?
The same ERS tower is not effectively used everywhere in the glove due to the geographical diversity in the world. So, ERS tower or ERS structure types are mainly
considered:
I.
support
mountain-to-mountain span;
II.
crossing the hot
and hard-packed sands in the desert area;
III.
Soft-soiled flood
plains territory.
What Specification Should Consider for ERS Tower?
The following specification should be considered for selecting an emergency restoration system (ERS) tower:
i.
the column
sections' workability of ERS;
ii.
the foundations
for erection ERS;
iii.
the articulating
gimbal joint of ERS tower;
iv.
the guy wire
specification;
v.
the guy wire
accessories;
vi.
the insulators;
vii.
the anchors to
balance the load;
viii.
the guy plates to
take sufficient tension;
ix.
the conductor hardware;
x.
Construction
tools;
xi.
other spare
parts;
xii.
computer software
and trained personnel.
What Standard Should Follow for ERS Structure?
ERS structure is principally used in an emergency situation. So, product quality considering safety must be the highest prioritized. Marinating international standard-there is the “IEEE Guide for the Design and Testing of Transmission Modular Restoration Structure Components”, including earlier or later versions. Strict conformance of IEEE 1070-2006 includes testing requirements, material requirements, fabrication requirements, and all other geometric and dimensional requirements listed in the IEEE 1070 standard, without exception. The manufacturer shall submit with his proposal, a certified copy of the Design Test Report as required in Section 4 of IEEE Standard 1070-2006.
Feature Components of ERS Structure
ERS
structure needs to contain the following feature components to make it easy and
simplified various configurations to comply with emergency system restoration:
a. light-weight to allow for manual
transportation;
b. different configurations;
c. Comply with IEEE Standard 1070-2006, “IEEE
Guide for the Design and Testing of Transmission Modular Restoration Structure
Components”;
d. minimizing the number of guy wires used to be;
e. welding complies with Section 3 of IEEE Standard
1070;
f. Testing complies with the IEEE Standard
1070-2006 “IEEE Guide for the Design and Testing of Transmission Modular Restoration
Structure Components”;
g. size and diameter of threaded fastener comply
with IEEE Standard 1070;
h. All used ferrous materials must be galvanized
complying with standard ASTM A153;
i. All Column sections must comply with IEEE
Standard 1070;
j. All column sections must be tested in
accordance with Sections 5.1 and 5.2 of IEEE Standard 1070;
k. All Foundation Plates, Gimbal Joint, Guy
Plates, Box Sections, and Insulators must be made in accordance with IEEE Standard
1070.
Listed Tools for Installation ERS Tower
A number of hydraulic tools and hand tools are required to assemble and erection ERStower:
A. Anchor Installation Tools
i.
gasoline
hydraulic power unit;
ii.
hydraulic driving
hammer;
iii.
hydraulic rotary
hammer;
iv.
hydraulic proof
testing unit;
v.
hydraulic hoses,
rock drill bits, torque installation tools, etc.
B. Construction Tools
i.
snatch blocks and
rigging ropes;
ii.
A ½ ton hydraulic
capstan winch with foot pedals;
iii.
high-quality
2-ton Tractel Tirfor-style grip hoists;
iv.
reversible
ratchet;
v.
six (6) to three
(3) ton reversible chain hoists;
vi.
pulling eyes;
vii.
automatic wire
grips;
viii.
double loop 6x37
steel wire rope slings;
ix.
self-contained 6-ton hydraulic wire cutter;
x.
foundation stakes;
xi. Aluminium
conductor lifting hooks, etc.
Testing and Commissioning:
After
installation must carry out the field testing and commission before going to
operate. This test may include visual, equipment-oriented, or even software
base computerization.
If
you think it is helpful then share it with your friends or put your valuable
comments to improve this article.
Subscribe to:
Posts (Atom)
You may like the following pages
-
How to Calculate PCD (Pitch Circle Diameter)? PCD is the short form of Pitch Circle Diameter ; the Pitch Circle Diameter (PCD...
-
What is Bus-bar? Bus-bar is the common header where one or multiple sources poor the power also one or more sources can take power simul...
-
Different Rating's Fuses Fuse Rating Calculating Guide The function of a fuse is to break a circuit when a current threshold...
-
Why Use Direct Online (DOL) and Star-Delta Starter? DOL means the motor is connected directly to the Line (Direct On Line) using one ...
-
Fig: Three Phase DB Wiring Diagram 3 Phase Electrical Distribution Board DB Wiring Procedure To understand and wiri...
-
Fig: Three Phase Motor connection diagram with a star-delta starter. What is Star Delta Starter for Motor Starting? Star-Delta start...
-
What Is Radial and Ring Circuits? Think of a simple Circle that has a radius and periphery. The electrical circuit in your wiring system...
-
Bangladeshi all National and Regional Bangla Newspaper List in a Single Click bdnews24.com Dhaka, B...
-
How Wire the Tube Light? A tube light or florescent tube wiring is simple but we frequently face questions with the issues- how to w...
-
Basic Colour Code for Electrical Cable and Power Cable International standard IEC 60446 developed basic and safety principle...