Range of type
approval:
Rated voltage range, cross-sectional area range,
constructional procedure, variation of calculated electrical stress at
conductor screen and insulation screen range condition should be met.
Electrical type tests:
Sponsored Link-
To pass the electrical type tests on a completed cable first of
all need to choose a piece of cable at least 10 meter length. Some series of
test as per IEC standard requirements need to performed on that piece of cable,
such as- bending test; tan lamda measurement test; heating cycle voltage test; lightning
impulse voltage test; partial discharge test at ambient temperature;
examination of the cable on completion of the these tests.
Test voltage values:
As per IEC standard 60840 test voltage values are shown
in the table, but important considering point is that ensure the insulation
thickness is correct as per IEC standard 60811-1-1 of the piece of cable which
used for test. If insulation thickness is not same as requirement, no problem,
just need to adjust the test voltage value as per insulation thickness.
 |
Table- Test Voltage Values |
Bending test:
As per IEC standard the bending test procedure is as below-
The cable sample shall be bent around a test
cylinder (for example, the hub of a drum) at ambient temperature for at least
one complete turn and unwound, without axial rotation. The sample shall then be
rotated through 180° and the process repeated.
This cycle of operations shall be carried out
three times in total.
The diameter of the test cylinder shall not be
greater than:
-for cables with plain aluminum
sheaths:
-36 (d + D) + 5 % for single-core
cables;
-25 (d + D) + 5 % for three-core
cables;
-for cables with lead, lead-alloy, corrugated
metallic sheaths or with longitudinally applied metal foils (overlapped or
welded) bonded to the over sheath:
-25 (d + D) + 5 % for single-core
cables;
-20 (d + D) + 5 % for three-core
cables;
-for other cables:
- 20 (d + D) + 5 % for single-core
cables;
-15 (d + D) + 5 % for three-core
cables.
Where
d is the nominal diameter of the conductor, in
millimeters;
D is the nominal overall diameter of the cable,
in millimeters.
NOTE:
A negative tolerance is not specified, but testing at diameters below
the specified values should only be done by agreement with the manufacturer.
Partial discharge test at ambient temperature:
Sponsored Link-
The partial discharge test performed as per
requirements of IEC standard 60885-3, in the table test voltage values the test voltage range is mentioned in column 5
as ‘partial discharge test’; the test
voltage shall be raised gradually to and held at 1.75 U0
for 10 second and then slowly reduced to 1.5 U0.
Tan lamda
measurement:
The procedure of tan lamda measurement is mentioned
in IEC 60840 is quoted in below- “The sample shall be heated by a suitable
method and the temperature of the conductor determined either by measuring its
resistance or by thermocouples on the surface of the screen/sheath, or by
thermocouples on the conductor of another sample of the same cable heated by
the same means. The sample shall be heated until the conductor reaches a
temperature which shall be 5°C to 10 °C above the maximum conductor temperature
in normal operation. The tan shall then be measured at a power frequency
voltage of U0 at the temperature specified above”.
Heating cycle voltage test:
Heating cycle test voltage is mentioned in table- test voltages
values are 2 times. Cable assembly as bending test/ U-bend, cable heated 5 to
10 degree above the conductor maximum temperature. Cable heated for 8 hours and
stay for 2 hours then natural cooling for 16 hours. This process carried out 20
times.
Lightning impulse voltage test:
The impulse voltage shall be applied according to the procedure
given in IEC 60230 on cable assembly heated 5 to 10 degree above the conductor
maximum temperature. This test
followed by a power frequency voltage test at 2.5 times of test voltage U0 for 15 minutes as shown column 4
in test voltage values table.
Examination:
Physical check and examination is carried out during test,
if there any degradation visible in cable.
Resistivity of semi-conducting screens:
This measurement of resistivity of semi-conducting test is
carried out on separate piece of cable.
Non-electrical type tests:
The non-electrical type test may perform by checking and
testing as follow:
-Cable construction;
- Mechanical properties of insulation;
- Mechanical properties of over sheaths;
- Compatibility of materials;
- Mass test on PVC over sheaths;
- Pressure test at high temperature on over sheaths;
- PVC over sheaths low temperature test;
- Heat shock test for PVC over sheaths;
- Ozone resistance test for EPR and HEPR insulations;
- Hot set test for EPR, HEPR and XLPE insulations;
- Density of HDPE insulation;
- Carbon black content of black PE over sheaths;
- Shrinkage test for PE, HDPE and XLPE insulations;
- Shrinkage test for PE over sheaths;
- Hardness of HEPR insulation;
- Elastic modulus of HEPR insulation;
- Fire conditions test;
- Water penetration test, etc.
After completed the type test of sample for a series of cable (considering the cross sectional area of cable, voltage rating of cable, construction procedure of cable etc.) it is considered that the other cables within the same series are valid and certified that no need separate test for individual lot.