Why is a auxiliary Unit Transformer and a Station Transformer used?

What is the function of a station transformer and auxiliary transformer in Power Plant and Power Station?

If you work in a power plant or power grid station or familiar with such kind of power generation or power transmission system, you must know the function of station transformer or auxiliary transformer. I feel obliged to answer this question for them who are little bit far from these kind of working field. 

Let you make more easy to understand the station transformer, assuming that you have some basic knowledge about how a power plant or power grid station or substation works. Electrical or mechanical any device may go out of work in any time. In such situation you cannot afford a plant shut down due to failure of any device. 

Hence arrangements are made such that each and every device or facility has a back up. Station and auxiliary transformers are also a part of such arrangement.

Station or auxiliary transformers are invariably used in all Grid Sub-Stations & Power Plant. The KVA ratings of station transformer is normally 100 KVA, 33/0.4 KV. It is connected to the 33 KV Main /Transfer Bus bar in the Grid substation with required protection & control.

Single Line Diagram of Auxiliary Unit Transformer 

Auxiliary Unit Transformer
Station transformers are that transformers in which input is from the generator and output goes to the bus bar. And auxillary transformers are those which are used for the auxillary machines which are used inside the plant to run the plant.

The Station Transformer is used for 

In any power plant, station transformer will get the supply from the grid to provide supply to the auxiliaries which are common to all the units, all illumination of Sub-Station yard & Control Room. Other loads such as ceiling fan, exhaust fans are also met from Station Transformer

Station Transformer supply is used for Battery Charging too.

Rutine works like cooling sysytem usingg external fan for transformers, airconditioning of control room, equipments include Oil Filtration machine, Drilling machine, Grinder machine for sharpening Tools & Plants etc.

Power supply ,required for Civil work for Mixture machine, Vibrator etc are met from Station Transformer and any other temporary works that may come where power supply is required.

Unit Auxiliary Transformer is used for 

An auxiliary transformer is a smaller transformer than the main supply transformer in a piece of equipment is commonly used to energise a master control relay which switches on the main supply.

The Unit Auxiliary Transformer is same to other Power Transformer that provides power supply to the auxiliary equipment of a power plant or power generating station or power grid station or power grid substation during its normal operation. UAT is connected directly to the generator out-put or High voltage or Extra high voltage incomming bus by a tap-off of the isolated phase bus duct and thus becomes cheapest source of power to the generating station.

UAT or Unit Auxiliary Transformer is generally a three-winding transformer i.e. one primary and two separate secondary windings. Primary winding of UAT is equal to the main generator voltage rating. The secondary windings can have same or different voltages i.e. generally 11KV and or 6.9KV as per plant layout.

Unit Auxiliary Transformer [UAT] will get the Supply from Generator Transformer which is charged only when the unit is running. If unit is not running then UAT gets the supply from the station transformer.

These transformers are connected to the Generator Transformer bus. These transformers steps down the voltage from 230kV or 400kV to 6.6kV (230/6.6kV or 400kV/6.6kV) and supply the power to the electrical auxiliaries present in the plant (motors, drives, lighting and other plant loads as descrived above in station transformer).

Station service voltage transformer SSVT 

ABB developed the the alternate of auxiliary transformer called SSVT or Station Service Voltage Transformer, these captured market in North America and remains an innovator in this field with new designs. 

SSVT inductive voltage transformers consist of a single-phase design intended for connection between phase and ground on 46 kV-362 kV HV grounded neutral networks to supply power to panels at low voltage or medium voltage.

The design allows for convenient siting within the substation environment for simple mounting to single phase supports. The SSVT is directly connected to the HV network and provides power to the panel within the substation, or to remote loads directly supplied for the HV service.

Capacity ratings 46kV to 362kV

ABB also introduced SSVM, the meaning of SSVM is station service medium voltage transformer that a variation of the SSVT, the SSMV steps down the power from a high-voltage transmission line to a medium-voltage output. High side voltage classes range from 46 to 138 kV with a 15 kV output, and a maximum rating of 200 kVA. 

Applications of SSVT

  1. Station service auxiliary power needs;
  2. Railway applications for small power needs;
  3. Remote site power for small industrial loads or mining sites;
  4. Rural electrification for reducing the cost of first power.

Applications SSVM

  1. Rural / remote area electrification
  2. Oil and gas field power
  3. Railroad electrification
  4. Mining and construction power
  5. Hospital and defense installations
  6. Airports and transportation hubs

What is Auxiliary Load

Auxiliary Load means, in relation to a generating CMU or a generating unit, the total amount of electricity used by that unit for purposes directly related to its operation (including for fuel handling, fuel preparation, maintenance and the pumping of water), whether or not that electricity is generated by the unit or used while the unit is generating electricity.

What is Auxiliary Power?

Auxiliary power is electric power that is provided by an alternate source and that serves as backup for the primary power source at the station main bus or prescribed sub-bus. An offline unit provides electrical isolation between the primary power source and the critical technical load whereas an online unit does not.

No comments:

Post a Comment

WAZIPOINT:
Thank you very much to visit and valuable comments on this blog post. Keep in touch for next and new article. Share your friends and well-wisher, share your idea to worldwide.

You may like the following pages